Technical specifications

ТОЛ-ADL-40,5 УХЛ2

Parameter nameParameter value
Highest equipment voltage, Um [kV]40,5
Rated primary current, Inp [A]5; 10; 15; 20; 25; 30; 40; 50; 75; 100; 150; 200; 300; 400; 500; 600; 750; 800; 1000; 1200; 1500; 2000; 2500; 3000
Rated secondary current, Isn [A]1 or 5
Rated frequency, fn [Hz]50
Secondary winding accuracy class for metering0,2S | 0,2 | 0,5S | 0,5 | 1
Secondary winding accuracy class for protection5P; 10P; PX
Rated secondary burden at cos φ = 0,8 - metering winding [VA]5; 10; 15; 20; 30; 40; 50
Rated secondary burden at cos φ = 0,8 - protection winding [VA]5; 10; 15; 20; 30; 40
Instrument security factor, FSFS5 or FS10
Accuracy limit factor, ALF5; 10; 15; 20; 30
Number of secondary windings1; 2; 3; 4; 5; 6
Power-frequency test voltage [kV]95
Lightning impulse test voltage [kV]200
Rated insulation level according to DSTU EN 61869-2 [kV]40,5 / 95 / 200
Climatic configuration and installation category according to GOST 15150УХЛ2
Maximum installation altitude above sea level [m]1000
Installation typeIndoor installation
ConstructionCast epoxy insulation that does not support combustion
Maximum weight [kg]70
Minimum average service life [years]40
Switchable transformation ratio optionVersion with a switchable transformation ratio — on request
Compliance with standardsDSTU EN 61869-2:2017 “Instrument transformers. Part 2: Additional requirements for current transformers”